Isotherm Engineering provided mechanical, electrical, and controls commissioning services for a Humber College data centre supporting a multi-function academic facility. The scope focused on validating the performance of all energy-related and mission-critical systems in accordance with the OPR, BOD, and construction documentation.


Commissioning Levels (Cx 1–5)


A structured commissioning process was executed, including:


  • Installation verification and calibration
  • Start-up and pre-functional testing
  • Functional performance testing
  • Full-load integrated systems testing


Systems Commissioned


  • Multistack air-cooled chiller with primary pumps
  • Güntner dry coolers
  • APC in-row cooling units
  • Nortec humidification systems
  • Siemens DDC / BAS controls
  • Automatic Transfer Switches (ATS)
  • APC UPS systems
  • Emergency generators
  • Glycol/water loop TAB review and verification


Integrated Systems Testing Highlights


  • Data hall tested at 100% design load (160 kW)
  • Sequential failure testing of in-row cooling units to verify redundancy
  • Monitoring of chilled water temperatures, cold aisle temperatures, return air temperatures, and room humidity
  • Validation of automatic system response, alarm generation, and recovery during simulated fault conditions


Project Outcomes


  • Confirmed cooling and power resilience under part-load and full-load conditions (25%, 50%, 75% & 100%)
  • Verified alarm, control, and recovery sequences
  • Reduced operational and commissioning risk
  • Delivered a stable, reliable, and operationally ready data centre

Data Centre Commissioning Project - Humber College Etobicoke Campus

Client Name
: Humber College
Service
: New Construction Commissioning (NCx)
Status
: Completed